How to safe use the Carbon dioxide gas cylinders
1, Carbon dioxide system operating room should be kept clean and well ventilated, to have reliable lighting and communication equipment;
2, The room temperature should be kept at 0-45 ° C, no other items should be stored in the room, and unrelated personnel are not allowed to enter;
3, The gas cylinder should be checked and weighed once every 2 years, if the fire extinguishing agent is found to be reduced (1/10 of the total), it should be immediately added and recorded.
Every 5 years, the cylinder is inspected for corrosion and mechanical damage, and the hydraulic strength test is done according to the standard, and the performance can be continued to use. Piping should be tested every three years;
4. Use carbon dioxide to extinguish fire, especially when extinguishing engine room, cargo warehouse and other closed cabin fires, sound and light alarm should be issued before rescue to confirm that all personnel have been evacuated;
5, After the fire extinguished, the personnel should be thoroughly ventilated before entering the scene to prevent the occurrence of personnel suffocation accident;
6. After using carbon dioxide to extinguish the fire in the warehouse, the warehouse should not be opened prematurely for inspection, otherwise fresh air may lead to the re-ignition of the fire that has not been completely extinguished;
7. When using carbon dioxide to extinguish fires, water cannot be used at the same time to extinguish fires, because water can combine with carbon dioxide to become carbonic acid, which will reduce its fire-fighting performance.